Features

  • It controls up to 3 Air Conditioners
  • Separate phase supply for each AC
  • 3 Digit 7 Segment LED Display
  • Precise temperature sensing by Accurate Temperature Sensor
  • Time-sharing for the compressor to share the load equally
  • Separate alarm relay contact for high temperature
  • Password protection
  • Various set points are site suitable

Specifications

  • Supply Voltage 230 volts, 50 hz (+/- 15%)
  • Contact Ratings- 30 amp at 230 volt for compressor and 5 amp at 230 volt for alarm
  • Temperature sensor- NTC 10K @25C sensor cable length 2.75 Mtr.
  • Temperature sensing range .1°C to 50°C
  • Resolution – .1°C

Indication

  • Healthy Condition
  • Supply On for AC
  • Room High Temperature

Keypad

  • SET- To enter into function mode/ to view next parameter set point
  • UP- To increment the value of set point
  • Down – To decrement the value of set point
  • Enter – To come out of the function mode and accept the password and other values if changed

Mounting

  • Wall Mounting

Size

215X190X70 MM

Terminal Layout

  • Supply 230 Volt AC               –    L|N|E
  • AC1                                          –    C|NO
  • AC2                                         –    C|NO
  • High-Temperature  Alarm     –  C|NO
Innovative Products and Service for Industry.